Fault Code |
Fault Description |
Possible Causes |
Fault Code F1 |
Ignition Failure |
- Insufficient Inlet Working Gas Pressure At The Appliance
- Flue Problem
- Condensate Blockage
- Spark Generation Issue
- Incorrect Gas Valve Adjustment
- Flame Rectification Issue
- Poor Combustion
- Combustion Door Seal Leak
- Software Error On The Main PCB Or The User Interface PCB
|
Fault Code F2 |
Air Fault |
- Fan Fault
- Fan Wiring Harness Fault
- No Power To The Fan From The Main PCB
- No Power To The Fan From The DC Fan Transformer (Early Models Only)
- Replacement Main PCB Not Fitted Correctly By Service Engineer (DC Fan Transformer Bridging Card Not Fitted Correctly)
|
Fault Code F3 |
Air Fault |
- Fan Fault
- Fan Wiring Harness Fault
- No Power To The Fan From The Main PCB
- No Power To The Fan From The DC Fan Transformer (Early Models Only)
- Replacement Main PCB Not Fitted Correctly By Service Engineer (DC Fan Transformer Bridging Card Not Fitted Correctly)
|
Fault Code F4 |
Ignition Failure Or Flame Sensing Fault |
- Insufficient Inlet Working Gas Pressure At The Appliance
- Flue Problem
- Condensate Blockage
- Spark Generation Issue
- Incorrect Gas Valve Adjustment
- Lack Of Flame Rectification
- Poor Combustion/Flame Picture
- Combustion Door Seal Leak
- Software Error On The Main PCB Or The User Interface PCB
- Spark Generator Fault
|
Fault Code F5 |
Overheat Fault |
- The Overheat Thermostat Has Activated In The Appliance Due To Poor Circulation (115C)
- Pump Not Running
- Air Lock Within The Boiler Or The System
- Blockage Within The Boiler Or The System
- Heating Return Filter Blocked In Appliance (Cxi & Sxi Models Only)
- System Design Issue
- No Permanent Live Wired Into The Appliance Causing No Pump Overrun (Hxi Model Only)
- Pump Not Wired Directly Into The Appliance (Hxi Model Only)
- Insufficient System Bypass
- NTC Thermistor Out Of Calibration (Should Read 12Kohms @ 20C)
|
Fault Code F6 |
Heating Flow Thermistor Fault |
- The Heating Flow NTC Thermistor Has Gone Open Circuit (Should Read 12Kohms @ 20C)
- Wiring Harness Fault Or Connection Fault Between The Heating Flow Thermistor And The Main PCB
- Flow & Return Piped Up The Wrong Way Round (Hxi Model Only)
- External System Pump Circulating The Wrong Way Around The System (Hxi Model Only)
|
Fault Code F7 |
Domestic Hot Water Thermistor Fault (Cxi Model Only) |
- The Domestic Hot Water NTC Thermistor Has Gone Open Circuit (Should Read 12Kohms @ 20C)
- Wiring Harness Or Connection Fault Between The Domestic Hot Water Thermistor & The Main PCB
|
Fault Code F8 |
Not Applicable To This Appliance |
- If This Code Appears It Is Software Error On The Main PCB Or The User Interface PCB
|
Fault F9 |
Multiple Errors |
- Low Water Pressure Sensor Fault
- Overheat Thermostat Has Activated (Early Models Only)
- NTC Thermistor Fault (Should Read 12Kohms @ 20C)
- The Fuse Has Blown In The DC Fan Transformer Unit (Early Models Only)
- Incompatible Software on Main PCB or User Interface PCB
- Circulation Problem (If F9 Flashes On The Display & Then Resets Itself)
- Low Voltage Component Failure
- Connection Fault On The Low Voltage Component Wiring Loom
- Replacement User Interface PCB Has Not Been Set Up Correctly By The Service Engineer
|
Fault Code F10 |
Heating Return Thermistor Fault |
- The Heating Return NTC Thermistor Has Gone Open Circuit (Should Read 12Kohms @ 20C)
- Wiring Harness Fault Or Connection Error Between The Heating Return NTC Thermistor And The Main PCB.
|
Fault Code F11 |
Software Error On The Main PCB |
- Main PCB Fault
- Loose Wiring Connection On The Main PCB
- Domestic Hot Water Flow Sensor Fault (Cxi Model Only)
|
Fault Code F12 |
Software Errors |
- Fault On The Main PCB
- Fault On The User Interface PCB
- Faulty Domestic Hot Water Flow Sensor (Cxi Model Only)
- Faulty Water Pressure Sensor (Cxi & Sxi Models Only)
- Wiring Loom Fault
|
Fault Code F13 |
Software Or Electrical Error |
- Main PCB Fault
- User Interface PCB Fault
- Loose Or Damaged Connection On The Wiring Loom
- Insufficient Earth
- Low Voltage Component Failure
- Water Leak On The Diverter Motor (Cxi Model Only)
|
Fault Code F14 |
The Flow Pipe On The Main Heat Exchanger Is Greater Than 95 Degrees |
- Blockage Or Air Lock In The Appliance
- Pump Not Running
- System Circulation Fault
- Blocked Domestic Hot Water Heat Exchanger (Cxi Model Only)
- Heating Flow NTC Thermistor Out Of Calibration (Should Read 12Kohms @ 20C)
- External System Pump Not Wired Into The Appliance Causing No Pump Over-Run (Hxi Model Only)
|
Fault Code F15 |
Not Applicable To This Appliance |
|
Fault Code F16 |
Flame Detection Fault (Flame Presence For More Than 5 Seconds After Burner Stop) |
- Gas Valve Fault – (Flame Still Present After Demand Has Ceased)
- Software Fault On The Main PCB Or The Spark Generator Unit
|
Fault Code F17 |
Incoming Power Supply <170V |
- Incoming Power Supply Or Polarity Issue
- Fuse Blown In The DC Fan Transformer (Early Models Only)
- Main PCB Fault
- Incompatible Software (Incorrect PCB Fitted To Appliance)
|
Fault Code F18 |
User Interface PCB Fault |
- Check Cable Connection Between Main PCB & User Interface PCB
- User Interface PCB Fault
|
Fault Code F19 |
Insufficient Temperature Rise On Heating Flow Pipe After Ignition |
- Heating Flow NTC Thermistor Disconnected From The Flow Pipe Off The Main Heat Exchanger
- Diverter Valve Passing Into The Central Heating Circuit During Hot Water Demand (Cxi Model Only)
- Poor Heat Input Into The Heat Engine Causing Insufficient Temperature Rise (Low Inlet Working Gas Pressure, Gas Valve Incorrectly Adjusted, Burner Issue Etc)
- Domestic Hot Water Flow Rate Too Excessive
|
Fault Code F20 |
Incompatible Software |
- Wrong Main PCB Fitted Into The Appliance
- Wrong User Interface PCB Fitted Into The Appliance
- Wiring Harness Fault Between Main PCB & User Interface PCB
- Replacement User Interface PCB Has Not Been Set Up Correctly By Service Engineer
|
Fault Code F21 |
Not Applicable To This Appliance |
|
Fault Code F22 |
Not Applicable To This Appliance |
|
Fault Code F23 |
Not Applicable To This Appliance |
|
Fault Code F24 |
Heating Return Is Greater Than 90 Degrees |
- The Temperature On The Return Pipe On The Main Heat Exchanger Has Reached Over 90 Degrees
- Blockage Or Air Lock Within The Appliance
- System Design Fault
- System Circulation Fault
- Heating Pump Not Operating Correctly
- Heating Return NTC Thermistor Is Out Of Calibration (Should Read 12Kohms @ 20C)
- Boiler Piped Up The Wrong Way Round (Hxi Models)
|
Fault Code F25 |
Flow Temperature Rise Too High During Operation |
- The Temperature On The Main Heat Exchanger Flow Pipe Has Risen By 5 Degrees Per Second Due To A Blockage Or An Air Lock In The Appliance Or The System
- Pump Not Running
- Return Filter Blocked
- Heating Flow NTC Thermistor Is Out Of Calibration (Should Read 12Kohms @ 20C)
|
Fault Code F26 |
Maximum Temperature Differential Has Been Exceeded (>35 Degrees Celcius across Flow & Return) |
- System Design Fault
- Pump Not Running
- Air In The System Restricting Water Movement
- Debris In The System Restricting Water Movement
- The Heating Return NTC Thermistor Is Out Of Calibration (Should Read 12Kohms @ 20C)
|
2.7 Bar Or More Flashing On Display (Cxi & Sxi Models Only) |
High Pressure Fault |
- The Pressure In The Appliance Has Reached Over 2.7 Bar
- The Filling Loop Has Been Left On Or Is Passing
- Split Domestic Hot Water Heat Exchanger (Cxi Model Only)
- Central Heating System Is To Large For The Appliance
- Expansion Vessel Issue (Insufficient Air Charge Or Faulty Vessel)
- Expansion Vessel Supply Hose Is Blocked
- Incorrect Pressure Reading Being Shown Due To A Water Pressure Sensor Fault
|
0.5 Bar Or Less Flashing On Display (Cxi & Sxi Models Only) |
Low Pressure Fault |
- The Pressure In The Appliance Has Dropped To Below 0.5Bar
- Water Leak On The Boiler
- Water Leak On The System
- Incorrect Pressure Reading Being Shown Due To A Water Pressure Sensor Fault
|